Large Facility UPS
Liebert NX, 10 - 30kVA On-Line UPS
Quick links: Overview, Features and Benefits, Specifications, Other Photos
Liebert NX is a mid-sized, three-phase UPS system that delivers complete, centralized power protection for mission-critical systems. Designed to meet the high availability power needs of a wide variety of IT applications, the UPS combines compact size, advanced operating features and low cost of ownership.
The 120/208 Volt, three-phase, version of the Liebert NX is available in four sizes including 10, 15, 20 and 30 kVA capacities.
Flexibility:| Family Name | Liebert NX™, 10 - 30kVA | ||||
| Model Number | NX 10kVA-30kVA | NX Battery Cabinet 10kVA-30kVA | NX Maintenance Bypass Cabinet 10-30kVA | NX Parallel Cabinet 20kVA-30kVA | NX Slimline Distribution Cabinet 10kVA-30kVA |
| Power Rating | |||||
| Rating, kVA | 10, 15, 20 or 30 | N/A | 10, 15, 20 or 30 | 20 to 90 | N/A |
| Rating, kW | 8, 12, 16 or 24 | N/A | 8, 12, 16, 24 | 16 to 72 | N/A |
| Input AC Specifications | |||||
| Phase | 3 | N/A | 3 | 3 | 3 |
| Power Factor | Up to 0.99 lagging | N/A | N/A | N/A | N/A |
| Input Frequency, Hz | 50 or 60 | N/A | 60 | 60 | 60 |
| Frequency Range, Hz | +/- 5 Hz | N/A | N/A | N/A | N/A |
| Input Voltage | 120/208 | N/A | 120/208, 220, 480, 600 | 208, 480, 600 | 208/120 |
| General Specifications | |||||
| UPS Technology | On-line, double conversion | N/A | N/A | N/A | N/A |
| Battery Specifications | |||||
| Battery Test Type | On-Line | N/A | N/A | N/A | N/A |
| Battery Technology | VRLA, Wet Cells | VRLA | N/A | N/A | N/A |
| Output AC Specifications | |||||
| Nominal Voltage | 120/208 | 288 VDC | 120/208 | 120/208 | 120/208 |
| Output Frequency, Hz | 50 or 60 Hz | 60 | 60 | 60 | 60 |
| Output Waveform | Sinewave | Sinewave | Sinewave | Sinewave | Sinewave |
| Panelboards or Receptacles | N/A | N/A | N/A | N/A | 1 Panelboard (42-poles) |
| User Interface | |||||
| Display Type | LCD | N/A | N/A | N/A | N/A |
| Communications | |||||
| Communications Options | Liebert IntelliSlot, SNMP, Relay Card, Liebert MultiLink | N/A | N/A | N/A | N/A |
| Physical Data | |||||
| Color | PMS 877 | PMS 877 | PMS 877 | PMS 877 | PMS 877 |
| Form Factor | Stand Alone | Stand Alone | Stand Alone | Stand Alone | Stand Alone |
| Unit Height, inches (mm) | 63 (1,600) | 63 (1,600) | 63 (1,600) | 63 (1,600) | 63 (1,600) |
| Unit Width, inches (mm) | 24 (600) | 27 (686) | 27 (686) | 27 (686) | 11 (279) |
| Unit Depth, inches (mm) | 32.5 (825 ) | 32.5 (825) | 32.5 (825) | 32.5 (825) | 32.5 (825) |
| Unit Weight, lbs. (kg) | 450 (205) to 1250 (567) w/ internal batteries | 1,350 (612) to 3740 (1697) | 620 (281) to 1400 (635) | 904 (410) to 1912 (867) | 250 (115) |
| Shipping Height, inches (mm) | 69 (1,753) | 69 (1,753) | 69 (1,753) | 69 (1,753) | 69 (1,753) |
| Shipping Width, inches (mm) | 32 (813) | 35 (889) | 35 (889 ) | 35 (889 ) | 35 (889) |
| Shipping Depth, inches (mm) | 40 (1,016) | 40 (1,016) | 40 (1,016) | 40 (1,016) | 40 (1,016) |
| Shipping Weight, lbs. (kg) | 600 (273) to 1400 (635) w/ internal batteries | 1,500 (680) to 3940 (1787) | 770 (349) to 1550 (703) | 1104 (500) to 2112 (958) | 400 (182) |
| Environmental | |||||
| Operating Temperature, Minimum °F (°C) | 32 (0) | 32 (0) | 32 (0) | 32 (0) | 32 (0) |
| Operating Temperature, Maximum °F (°C) | 104 (40) | 104 (40) | 104 (40) | 104 (40) | 104 (40) |
| Storage Temperature, Minimum °F (°C) | -4 (-20) | -4 (-20) | -4 (-20) | -4 (-20) | -4 (-20) |
| Storage Temperature, Maximum °F (°C) | 158 (70) | 158 (70) | 158 (70) | 158 (70) | 158 (70) |
| Relative Humidity | 0% to 95%, Non Condensing | 0% to 95%, Non Condensing | 0% to 95%, Non Condensing | 0% to 95%, Non Condensing | 0% to 95%, Non Condensing |
| Operating Elevation, ft. (m) | to 3,300 (1,000 ) | to 3,300 (1000) | to 3,300 (1000) | to 3,300 (1000) | to 3,300 (1000) |
| Storage Elevation, ft. (m) | to 40,000 (12,200 ) | to 40,000 (12,200) | to 40,000(12,200) | to 40,000 (12,200) | to 40,000(12,200) |
| Sound Emission/Audible Noise | < 54 dBA, at 1 meter | N/A | N/A | N/A | N/A |
| Cooling | Fan Cooled | Convection Cooled | Convection Cooled | Convection Cooled | Convection Cooled |
| Agency/Certification/Conformance | |||||
| Agency Approval | UL 1778, c-UL, FCC Class A | UL 1778, c-UL, FCC Class A | UL 1778, c-UL, FCC Class A | UL 1778, c-UL, FCC Class A | UL 1778, c-UL, FCC Class A |
| Warranty | |||||
| Standard | 1 Year | 1 Year | 1 Year | 1 Year | 1 Year |