Home Products Power Distribution Units Network UPS Liebert NX, 40 - 200 kVA On-Line UPS

Liebert NX, 40 - 200 kVA On-Line UPS

Thumbnail

  • Scalable UPS protection for growing data centers
  • Offers models with capacity growth without increasing footprint
  • Allows parallel configurations for capacity or redundancy
  • Operates with up to 97% energy efficiency

Overview

Overview

Liebert NX UPS with Softscale™ technology is a true on-line, double conversion, three-phase UPS system that provides a scalable solution for growing data centers. The UPS allows growth from 40 to 60 to 80 kVA, from 80 to 100 to 120 kVA, and from 160 to 200 kVA. The UPS may also be paralleled for additional capacity or for redundant operation.

The 480 Volt, three-phase Liebert NX is available in both scalable and standard models:

  • Liebert NX with Softscale™ technology is a full-featured UPS available in scalable models: 40 to 60 to 80kVA, 80 to 100 to 120kVA, and 160 to 200 kVA. Up to three unlike or like capacities may be paralleled for capacity; up to four unlike or like capacities may be paralleled for redundancy.
  • Liebert NX fixed capacity models are available in 40, 60, 80, 100 and 120, 160 and 200 kVA.

Features & Benefits

Features & Benefits

Flexibility:
  • Provides an economical path for growth, with Softscale technology.
  • Allows paralleling of unlike capacities for capacity or redundancy.
  • Offers a large and user-friendly LCD display with operating information in twelve languages.
  • Includes a built-in automatic bypass to transfer the load in case of fault.
Higher Availability:
  • True on-line, double conversion technology corrects for all types of power fluctuations.
  • Provides the highest output power quality, with advanced inverter control technology.
  • Provides dual bus synchronization of two UPS units when feeding independent distribution paths.
Lowest Total Cost Of Ownership:
  • Optimizes efficiency using soft-switching technology.
  • Extends battery life with temperature-compensated battery charging.
  • DSP control provides highest possible input power factor for maximum efficiency.
Ideally Suited For:
  • Small to mid-size data centers
  • Server rooms
  • Production
  • Labs and testing
  • Telecommunications
  • Process control
  • Point of sale

Specifications

Specifications

Family Name Liebert NX™, 40 - 200 kVA
Model Number NX 40 kVA NX 60 kVA NX 80 kVA NX 100 kVA NX 120 kVA NX Battery Cabinet 40-120 kVA NX Parallel Cabinet Type E1 NX Parallel Cabinet Type E

Power Rating

Rating, kVA 40 60 80 100 120 80/120 80/120 80/120
Rating, kW 36 54 72 90 108 80/120 80/120 80/120

Input AC Specifications

Phase 3 3 3 3 3 2 3 3
Power Factor >0.99 at full load; >0.98 at half load >0.99 at full load; >0.98 at half load >0.99 at full load; >0.98 at half load >0.99 at full load; >0.98 at half load >0.99 at full load; >0.98 at half load N/A N/A N/A
Input Frequency, Hz 50 or 60 Hz 50 or 60 Hz 50 or 60 Hz 50 or 60 Hz 50 or 60 Hz N/A 60 60
Input Voltage 480, 3 wire plus ground 480, 3 wire plus ground 480, 3 wire plus ground 480, 3 wire plus ground 480, 3 wire plus ground N/A 480V or 600V, 3 wire plus ground 480V or 600V, 3 wire plus ground

General Specifications

UPS Technology On-line, double conversion On-line, double conversion On-line, double conversion On-line, double conversion On-line, double conversion N/A N/A N/A

Battery Specifications

Battery Test Type On-line On-line On-line On-line On-line N/A N/A N/A
Recommended Operating & Storage Temperature Range N/A N/A N/A N/A N/A 74°F – 80°F (23°C-27°C) N/A N/A
Battery Technology VRLA, Wet Cells VRLA, Wet Cells VRLA, Wet Cells VRLA, Wet cells VRLA, Wet cells VRLA N/A N/A

Output AC Specifications

Nominal Voltage 480VAC, 3 wire plus ground 480 VAC, 3 wire plus ground 480 VAC, 3 wire plus ground 480 VAC, 3 wire plus ground 480 VAC, 3 wire plus ground 480 VDC 480 VAC, 3 wire plus ground 480 VAC, 3 wire plus ground
Output Frequency, Hz 60 (50 Hz in frequency converter mode) 60 (50 Hz in frequency converter mode) 60 (50 Hz in frequency converter mode) 60 (50 Hz in frequency converter mode) 60 (50 Hz in frequency converter mode) N/A 60 60
Output Waveform Sinewave Sinewave Sinewave Sinewave Sinewave N/A Sinewave Sinewave
Panelboards or Receptacles N/A N/A N/A N/A N/A N/A 1 1

User Interface

Display Type LCD LCD LCD LCD LCD N/A N/A N/A

Communications

Communications Options Liebert IntelliSlot, SNMP, Relay Card, Liebert MultiLink Liebert IntelliSlot, SNMP, Relay Card, Liebert MultiLink Liebert IntelliSlot, SNMP, Relay Card, Liebert MultiLink Liebert IntelliSlot, SNMP, Relay Card, Liebert MultiLink Liebert IntelliSlot, SNMP, Relay Card, Liebert MultiLink Dry Contact (back to UPS) Dry Contact (back to UPS) Dry Contact (back to UPS)

Physical Data

Form Factor Rack Rack Rack Rack Rack Rack Rack Rack
Unit Height, inches (mm) 78.5 (2000) 78.5 (2000) 78.5 (2000) 78.5 (2000) 78.5 (2000) 78.7 (2000) 78.7 (2000) 78.7 (2000)
Unit Width, inches (mm) 23.6 (600) 23.6 (600) 23.6 (600) 23.6 (600) 23.6 (600) 33.2 (845) 48.8 (1240) 33.2 (845)
Unit Depth, inches (mm) 38 (965) 38 (965) 38 (965) 38 (965) 38 (965) 38 (965) 38 (965) 38 (965)
Unit Weight, lbs. (kg) 1290 (585) 1290 (585) 1290 (585) 1422 (645) 1422 (645) Weight based on selected configuration Weight based on selected configuration Weight based on selected configuration
Shipping Height, inches (mm) 84.5 (2146) 84.5 (2146) 84.5 (2146) 84.5 (2146) 84.5 (2146) 84.5 (2146) 84.5 (2146) 84.5 (2146)
Shipping Width, inches (mm) 48 (1220) 48 (1220) 48 (1220) 48 (1220) 48 (1220) 48 (1220) 74 (1880) 48 (1220)
Shipping Depth, inches (mm) 48 (1220) 48 (1220) 48 (1220) 48 (1220) 48 (1220) 48 (1220) 54 (1372) 48 (1220)
Shipping Weight, lbs. (kg) 1490 (676) 1490 (676) 1490 (676) 1622 (736) 1622 (736) Weight based on selected configuration Weight based on selected configuration Weight based on selected configuration

Environmental

Operating Temperature, Minimum °F (°C) 32 (0) 32 (0) 32 (0) 32 (0) 32 (0) 32 (0) 32 (0) 32 (0)
Operating Temperature, Maximum °F (°C) 104 (40) 104 (40) 104 (40) 104 (40) 104 (40) 104 (40) 104 (40) 104 (40)
Storage Temperature, Minimum °F (°C) -4 (-20) -4 (-20) -4 (-20) -4 (-20) -4 (-20) -4 (-20) -4 (-20) -4 (-20)
Storage Temperature, Maximum °F (°C) 158 (70) 158 (70) 158 (70) 158 (70) 158 (70) 158 (70) 158 (70) 158 (70)
Relative Humidity 0% to 95%, non condensing 0% to 95%, non condensing 0% to 95%, non condensing 0% to 95%, non condensing 0% to 95%, non condensing 0% to 95%, non condensing 0% to 95%, non condensing 0% to 95%, non condensing
Operating Elevation, ft. (m) Up to 3,300 (1000) per IEC 62040/3 Up to 3,300 (1000) per IEC 62040/3 Up to 3,300 (1000) per IEC 62040/3 Up to 3,300 (1000) per IEC 62040/3 Up to 3,300 (1000) per IEC 62040/3 Up to 3,300 (1000) per IEC 62040/3 Up to 3,300 (1000) per IEC 62040/3 Up to 3,300 (1000) per IEC 62040/3
Sound Emission/Audible Noise 62 62 62 64 64 N/A N/A N/A
Cooling Fan Cooled Fan Cooled Fan Cooled Fan Cooled Fan Cooled Convection Cooled Convection Cooled Convection Cooled

Agency/Certification/Conformance

Agency Approval UL 1778, cUL, FCC Class A UL 1778, cUL, FCC Class A UL 1778, cUL, FCC Class A UL 1778, cUL, FCC Class A UL 1778, cUL, FCC Class A UL 1778, cUL, FCC Class A UL 1778, cUL, FCC Class A UL 1778, cUL, FCC Class A

Warranty

Standard 1 Year 1 Year 1 Year 1 Year 1 Year 1 Year 1 Year 1 Year

Other Photos

Other Photos

ThumbnailThumbnailThumbnailThumbnailThumbnailThumbnail

 

Login

Login or register to access our Knowledge Center and other Technical Resources.

MiraNews

Mirapath is sponsoring The Data Center Summit, which is a partnership between the Silicon Valley Leadership Group, the California Energy Commission and the Lawrence Berkeley National Lab.

The Data Center Efficiency Summit is a one day forum that focuses on best practices and emerging technologies/applications that reduce data center costs and significantly increase efficiencies for both legacy and new construction.

Data Center operators present case studies on their efficiency projects accompanied by actual results and ROIs. Projects cover both IT optimization options and facilities related energy efficiency improvements that increase data center efficiencies.

Read more...