Blue Server Deployment Power Calculator

How many servers can a 208V 30Amp feed support compared to a 208V 60amp 3 phase? Well, it depends.

We created a calculator that easily shows you how many servers a particular circuit can support, depending on the server power draw.

Note:

  1. We de-rated the circuit capacity by 80%.
  2. Assumed power factor of 1.
  3. Assumed 3 phase power is balanced.
  4. If using nameplate server power rating, the actual power draw can be 20%-50% less. Each server manufacturer has its own specifications.

Click here to use the calculator

In This Issue

Blue Featured Article
Yellow Mirapath Lunch & Learn Recap
Green New Product: Cisco Nexus 7010 & Smart CDU CS[CL]-6HD
Orange Recent Articles
Orange Ten Steps to Increasing Data Center Efficiency and Availability through Infrastructure Monitoring
Orange Multiple Rackmount UPS units or one Standalone UPS?
Orange Data Center Asset Management and DCIM
Orange Choosing the Right Server Rack

Server Deployment Power Calculator

We also have a complete table that outlines these different calculations. If you would like to receive a copy of the chart please email  This e-mail address is being protected from spambots. You need JavaScript enabled to view it

At Mirapath, we are committed to helping our customers find the right solutions for their current requirements, while also factoring in future needs to avoid costly retrofits. To discuss your power requirements, please reach out to one of our solutions specialists at This e-mail address is being protected from spambots. You need JavaScript enabled to view it .

Yellow Recap: Tour of the “Coolest” Co-location Facility in Silicon Valley

Mirapath Lunch & Learn

Our July Lunch & Learn event at Bay Area Internet Solutions (BAIS) was a great success! Thank you to everyone who was able to attend and make all of our efforts worthwhile.

To request a copy of the presentation covering power and cooling with photos showcasing BAIS' unique build, please contact one of our sales representatives at 877.647.2728 or by emailing This e-mail address is being protected from spambots. You need JavaScript enabled to view it . Below are the topics that were covered during the Lunch & Learn event.

Unique solutions used at BAIS and savings

  • Air side economizers, with dew point humidity control systems
  • Cold aisle containment pods
  • Precision cooling, installed servers are provided with consistent air over the entire height of the cabinets
    • 100% separation of cold and hot air
    • Achieving 70% energy reduction using pod enclosures versus non-container
    • Multiple utility feeders to different sub-stations
    • Tier IV Electrical & Mechanical system with no single points of failure
    • Savings of over 4.5 million Kilowatt hours of electricity annually with Cold Aisle Containment and Economizer Design
    • 1.3 PUE

Other topics of discussion

  • How to choose the right UPS system
  • Power management solutions
  • Monitoring and Control via DCIM solutions
  • Rack selection process

Green Looking for a solution to power the Cisco Nexus 7000 series?

Server Tech CS-6HD/HYIntroducing the unique Server Technology 50/60A 3-phase Smart CDU designed especially for Cisco Nexus 7000s. Sentry CS-6HD/HY products provide a NEMA locking outlet solution for high density applications found in data center cabinets. Server Technology CDUs provide reliable 3-phase power distribution combined with local and remote power monitoring and environmental monitoring via IP.

  • Form Factor: 2U Vertical
  • Voltage: 208V 3-Phase
  • Amps: 50/60 Amps
  • Input Plug: Single input feed
  • Output Plug: 6 x NEMA L6-30R

Learn more: Server Tech Smart CDU CS-6HD for the Cisco Nexus

Contact a Mirapath solution specialist for your specific application at 877.647.2728 or email This e-mail address is being protected from spambots. You need JavaScript enabled to view it .

Orange Recent Articles

Orange Ten Steps to Increasing Data Center Efficiency and Availability through Infrastructure Monitoring
We strive to bring you information that is interesting, relevant, and helpful in managing your data center and lab more efficiently. The following white paper by Emerson Network Power offers “Ten steps to Increasing Data Center Efficiency and Availability through Infrastructure Monitoring.” Although the article is written with Emerson solutions in mind, the insights the article provides are vendor neutral and other vendors provide similar solutions. In the article, we have highlighted the sections we found most interesting.
Click here to read more.

Orange Multiple Rackmount UPS units or one Standalone UPS?
Scenario: You have been using the 3000VA or 5000VA rack mount UPS units. Now, you are expanding. You need to add a few more racks and another couple of the 3000VA units. Also, you need to replace the batteries on the existing UPS units since it has been a couple of years since initial purchase. Should you add additional 3000VA rack mount UPS units or consider a standalone 3 phase UPS units?
Click here to read more.

Orange Data Center Asset Management and DCIM
Find out what data center infrastructure management (DCIM) tools are being implemented in the industry today.
Click here to read more.

Orange How to Choose the Right Server Rack
The server rack/cabinet is the cornerstone of a state of the art data center and lab. Choosing the right rack will not only make the difference in how the data center looks, but it will also positively impact the server network gear deployment process, promote good airflow, ease of equipment moves, and help with security initiatives. Because we know that choosing the wrong rack can be costly, we have put together some of the most common requirements that need to be taken into consideration when selecting a rack enclosure for your data center or lab...
Click here to read more.

Channel Partners

Mirapath is on Facebook and Twitter. Follow us for news, tech tips, product reviews, and internet-only specials

facebook twitter linkedin

Logo
877.647.2728
This e-mail address is being protected from spambots. You need JavaScript enabled to view it


Corporate Headquarters
10950 North Blaney Avenue
Cupertino, CA 95014
 
Copyright 2011 Mirapath Inc. All Rights Reserved